 | |  | |  | |  | | |  | |  | |  | |  | | |  | T:LAN NetStream 24x2 WAN, 4 Ethernet, 2 or 4 Serial ports, Dual WAN PipeLine mode, VLAN mapping |  |



 | |  |  | |  | |  | |  | | |  | RIO 1608R8S4B16 Digital, 8 Analog Inputs, 8 Relay Outputs, 4 Serial Ports |  | | |  | |  | | |  | RIO 4002R8B40 Digital, 2 Analog Inputs, 8 Relay Outputs |  | |  | |  | | |  | |  | | |  | |  | | |  | |  |



 | T:LAN Remote CommanderSee how the T:LAN Remote Commander facilitiates remote management and maintenance of the entire T:LAN product family. |  |  | |  |  | |  |  | Optima's SDCoIPOptima's SDCoIP can dramatically shorten turnaround times when techs respond to network problems and saves money in the process. |  |  | WAN PipelinesEasily aggregate WAN circuits for superior bandwidth utilization with the Optima T:LAN NetPlex/NetStream Series.
|  |







|
 |


FEATURES- 40 Discrete Alarm Inputs
- 2 Analog Inputs
- 8 Solid State Relay Outputs
- VT100, Telnet, SNMP Manageable
- Low Power, Compact Design
TECHNICAL SPECIFICATIONSPHYSICALWidth20.32cm (8.00”)
Height2.54cm (1.00”)
Depth6.99cm (2.75”)
Weight~550g
MountingRack mounting: 1U. Two units can be installed side-by-side using an optional bracket for standard 19” rack installations. Also supports tabletop, shelf and wall mounting.POWERInput5VDC, max. 50mA No separate power supply required as RIO modules are powered from Optima T:LAN unit.
Power ConsumptionLess than 1/4 Watt
ConnectorPower fed to module through the datacom RJ45 jack.ENVIRONMENTALTemperature0 to 50ºC (32 to 122ºF)
HumidityUp to 80% relative humidity (non-condensing)DATAConnectorDual RJ45, shielded
TypeOptima proprietary: communication with the first RIO Base module is through the T:LAN Expansion Port. Additional RIO Base modules are daisy chained from the first via their dual RJ45 interface jacks. RIO Expansion modules connect to RIO Base modules via an inter-module base expansion header.
DistanceUp to 10m (30ft)
CablingUTP, Category 5 (wired EIA568B standard straight-through)CONTACT INPUTSInputs40 ground referenced, triggered by switching to ground or applying a negative voltage
Voltage ToleranceUp to -60VDC
WiringOne contact per pair (24 contacts/connector)
ConnectorDual 25-pair Telco Connectors (female)
CablingUTP, Category 3 or better recommended | ANALOG INPUTSInputs2 single ended
Sensing RangeInput 1: -6.4VDC to +6.4VDC Input 2: -64VDC to +64VDC
ResolutionInput 1: 50mVDC Input 2: 0.5VDC
Wiring/ConnectorLast pair of each 25-pair connector
CablingUTP, Category 3 or better recommendedRelay OutputsOutputs8
TypeForm A
Voltage ToleranceUp to 300VAC or 300VDC
Switching100mA max., 30W (Resistive Load only)
WiringOne relay output per pair (on pairs 17-24 of second 25 pair connector)
Connector25-pair Telco Connector (female)
CablingUTP, Category 3 or better recommendedTemperature sensorRange/Resolution-55ºC to +100ºC, 0.0625ºCINDICATORLEDPower/Error/ActivityMANAGEMENTProtocolsVT-100, TELNET and SNMP through Optima T:LAN unit |

|
Related Files


|
|