Optima Releases T:LAN NetPro OS Update - October 2018

Optima Releases T:LAN NetPro OS Update - October 2018

REFERENCE: 

Optima Document Number: 4000-T200057A

DATE: 

November 02, 2018

DESCRIPTION: 

Optima has just released the T:LAN NetPro OS Update for October 2018. This version provides a minor bug fix. For more information, please refer to the associated OS release notes or check out the WHAT’S NEW section below.

T:lan OS Details

VERSION: 1.06.73A

RELEASE: C4418

BUILD: 7624

RELEASE DATE:

November 02, 2018

IMAGE NAMES:

NETPRO
Revision File Size
Rev.3x npe4x...1673AC4418... .rom 467,572
Rev.4x np44x...1673AC4418... .rom 537,928

Compatibility:

This release is suitable for the following models/units:
  • Optima T:LAN NetPro e42/e44, Rev.3x,
  • Optima T:LAN NetPro e42/e44, Rev.4x

Requirements:

For best results, use in conjunction with Optima Remote Commander Client (RCC) Version 3.11.0.356 (or newer).

NOTE: All T:LAN/RIO Embedded OS ROM files are covered by the Optima Embedded Software

License Agreement. By using the provided T:LAN/RIO Embedded OS ROM file you acknowledge that you have read and understood the Optima Embedded Software License Agreement, and you agree to be bound by it.

What's New:

FIXES
ID Scope Description
6000-S4001106 RIO Correctly Logs DC Inputs A/B Alarm Events

Recognized Dc Input A/b Voltage Level Alarms Are Not Always Logged

BACKGROUND:

Rev.3x/4x T:LANs (running OS versions up to and including BN7622) fail to log all DC Input A/B alarm events (if instrumented/enabled).

T:LAN OS BEHAVIOUR:

The RIO Node 0 correctly senses the crossing of the user defined DC Inputs A/B alarm thresholds. However the events will not always be logged in the RIO Event Log. As a consequence, no SNMP traps/notifications are being sent out following the detection of the actual event.

The units will only recognize and log the events when the T:LAN is re-booting or when the user re-enables the RIO handling.

AFFECTED UNITS:

All Rev.3x/4x T:LANs WITH instrumented DC Inputs A or B.

REMEDY:

Impacted units require a T:LAN OS update to BN7624 to guarantee proper DC Input A/B event logging.

Authorized users can now download the latest T:LAN OS firmware files via the Optima Cloud Storage.

NOTE: OCP operation is not impacted by the fixes/changes incorporated in BN7624

                